Sealevel Support http://www.sealevel.com/support/category/162 en-us KnowlageBase RSS Generator Interfacing Analog Signals to SeaI/O-570 Modules http://www.sealevel.com/support/article/AA-00489 Overview
The SeaI/O-570 A/D inputs can measure signals from a variety of sensors including accelerometers, flow meters, photocells, strain gauges, thermocouples, and thermistors. This makes the SeaI/O-570 ideal for applications such as measuring force, pressure, temperature or weight. The analog inputs on the SeaI/O-570 support floating, non-referenced signals or ground referenced signals, and can operate in unipolar or bipolar modes. The analog input modes and additional settings can be configured and verified via Sealevel SeaMAX software, which includes the SeaMAX API, MaxSSD utility, and Modbus support. Additionally, a dipswitch on the PCB enables a bias voltage of +5 through a 10K ohm resistor for thermistor input mode.


Floating Signal Source Wiring Guide
A floating, non-referenced signal source is a signal that is not connected in any fashion to the building ground system but rather has an isolated ground reference point. Examples of floating signal sources are outputs of transformers, thermistors, and battery-powered devices. To measure these devices, the ground reference point must be set to the analog ground reference of the SeaI/O-570 as shown in the below schematic. Without this connection, the signals will float and an accurate measurement is not possible. The SeaI/O-570 is configured to measure floating, non-referenced signals by default.


Ground-Referenced Signal Sources Wiring Guide
A ground-referenced signal is a signal that is connected in some fashion to the building system ground and therefore is already connected to a common ground point with respect to the SeaI/O-570. Examples would be non-isolated outputs of instruments and devices that are connected to the same building power system as the SeaI/O-570. The difference in ground potential between two devices connected to the same building power system is typically 1mV to 100mV and can be much higher with improper power system grounding. This ground potential difference can show up as a measurement error without using the proper measurement connections. The connection scheme below is designed to eliminate this ground potential difference from the measurement. This setting can be configured and verified via Sealevel SeaMAX software.



Thermistor Inputs
On the SeaI/O-570 PCB, Switch 5 (SW5) allows each of the eight A/D channels to be individually configured for a thermistor by moving the corresponding channel selector (1-8) to the “On” position. This will apply a bias voltage of +5V through a 10K Ohm resistor. Connect the thermistor between the input and ground reference on the SeaI/O-570’s terminal block connector. This will create a voltage divider and as the resistance of the thermistor changes so will the voltage read by the application. Please reference the data sheet of the chosen thermistor to calculate the measured temperature.



]]>
Wed, 09 Mar 2011 20:40:26 -0500
How to Switch Highly Inductive Loads Using Digital I/O http://www.sealevel.com/support/article/AA-00470

Application Example:

Highly inductive loads, those that use magnetic fields such as DC motors, produce a surge of voltage (referred to as "blowback voltage") when a relay is opened, breaking power to the electrical circuit. This surge of blowback voltage is created by the collapsing of the armature coil's magnetic field. In cases with large or higher wattage motors, this can cause an overvoltage condition on the motor and could cause the relay contacts to arc and possibly fuse. To protect against this overvoltage condition, care must be taken to dissipate the energy stored in the DC motor's coil when power is removed and there is no longer a path for current to flow.

In this example, we will demonstrate why an open-collector output with a flyback diode is better suited for controlling applications that are considered highly inductive.

Application Explanation

Reed Relay Implementation

Figure 1 shows a simple circuit for controlling power to a 24V typical DC motor using a Reed relay on a Sealevel SeaI/O-440U distributed I/O module. For this example, we will use an oscilloscope to measure the voltage change when power is removed (turned off) using this circuit.

Figure 1

Image: Reed Relay Output Diagram


Figure 2 represents a graphic from an oscilloscope measurement of the voltage spike that is induced at the Reed relay terminals when the relay is opened, removing power from the DC motor. This graph shows a delta voltage (delta Y on the screen) of 127V. During testing there were approximately 200V (delta) spikes routinely observed when the Reed relay is turned from on to off, indicating that the Reed relay did not properly dissipate the highly inductive load energy from switching the DC motor's power.

Figure 2

Image: Oscilloscope of Reed relay with inductive load


Open Collector Output

Figure 3 shows a circuit for a controlling a 24V DC motor with Sealevel's SeaI/O-540U open-collector output module with integrated flyback diode controlling power:

Figure 3

Image: Open-Collector Output Diagram

Figure 4 shows a graphic using an oscilloscope measurement of the voltage change that is induced when power is removed from the DC motor when using an open-collector output from the SeaI/O-540 module. During the open-collector output testing, the largest observed voltage change was 30V DC at the output terminal.

Figure 4

Image: Oscilloscope of open-collector with flyback diode switching inductive load


Conclusion

When power is removed from a highly inductive DC motor, the motor's blowback voltage must be properly dissipated to avoid damage to the electrical control circuit and/or the DC motor. This example clearly verifies that our open-collector output with a flyback diode circuit works very well at controlling highly inductive load energy associated with DC motors.

Sealevel's SeaI/O-530 and SeaI/O-540 modules use open-collector outputs with integrated flyback protection diodes making them a good choice for this application. The flyback diode provides a path for current to flow and dissipate in these conditions.

If Reed relays are used for moderate inductive load applications, they may require employing circuit protection measures. Reed relays are perfectly suited for a broad range of control applications but are not typically called upon as a solution for highly inductive loads.


Equipment Specifications:

DC motor: Pittman/CPR: 500
Power supply: Bench top 24VDC
Oscilloscope: Rigol DS1052E

SeaIO-540U: (32) Open-Collector Outputs (each containing a flyback protection diode)
SeaIO-440U: (32) Form A - Reed Relay Outputs


]]>
Mon, 15 Nov 2010 22:15:31 -0500
How To Control a Pro CD Player with Digital I/O http://www.sealevel.com/support/article/AA-00137

Hardware: A PC with Sealevel DIO-16.PCI Adapter (Part# 8002) or USB SeaLINK (Part# 8208), connected to Sealevel TB02 terminal block with CA112 cable. The TB02 and CA112 cable are available in a kit as Part# KT101.

PC with TB02 controlling pro series CD player

Software Control: Reed Relay output provides contact closure to ground (common) causing the CD player to enter the selected mode of operation (Play, Pause, Stop, Forward, or Reverse).


]]>
Wed, 09 Dec 2009 13:57:08 -0500
Test Applications with the Digital I/O Simulator http://www.sealevel.com/support/article/AA-00136

Hardware:A PC with Sealevel PIO Adapter (Part# 8005, 8008, 8009, 8010) or USB SeaLINK (Part# 8203, 8205), connected to Sealevel TA01, Relay Rack I/O Simulator terminal block with CA167 cable. The CA167 cable from the PC to terminal block is available as an option.

PC with TA01 Relay Rack Simulator

Software Control: Run VBTest or VCTest to cause the LEDs to turn ON and display the switch inputs. Set the ports to input or output through the control panel. Use the TA01 to develop your application program and simulate a solid state relay rack before going live on-site.

VBTest

VBTest

VCTest

VCTest


]]>
Wed, 09 Dec 2009 13:56:43 -0500
Control Industrial Devices with USB Digital I/O http://www.sealevel.com/support/article/AA-00135

Hardware: A PC or Laptop with Sealevel SeaLINK USB PIO-48 Adapter (Part# 8203) connected to an industry standard relay rack on DIN rail mounting track controlling a light pole or other industrial device. The USB cable (Part# CA179) is included with the 8203. Ribbon cables (Part# CA167) can be used to connect the 8203 to up to two standard PB24 style relay racks.

PC with 8203-DIN and Industry Standard Relay Rack

Software Control: Our included VCTest and VBtest sample applications can be used to control relay closure and input monitoring.

VBTest

VBTest

VCTest

VCTest


]]>
Wed, 09 Dec 2009 13:56:27 -0500
Control a DC Fan with a Digital I/O Relay http://www.sealevel.com/support/article/AA-00134

Hardware: A PC with Sealevel PLC-16.PCI (Part# 8011) board installed, connected to Sealevel TB08 terminal block. The cable from the PC to terminal block is supplied.

PC with TB08 and 12V fan

Visual Basic Application to turn on fan:

Visual Basic application to turn on fan


]]>
Wed, 09 Dec 2009 13:56:11 -0500
How to connect buttons & LEDs to Digital I/O http://www.sealevel.com/support/article/AA-00132

Hardware: A PC with Sealevel PIO-48.PCI (Part# 8005) or USB SeaPORT PIO-48 products, connected to Sealevel TB07, terminal block with CA167 cable. The cable from the PC to terminal block is available as an option.

PC with TB07

Software Control:Run VBTEST or VCTEST to monitor switch inputs. Click on Outputs (B0) to turn LED #1 ON/OFF. Click on outputs (B1) and (B2) to turn LED #2 from Red to Green.

VBTest

VBTest

VCTest

VCTest


]]>
Wed, 09 Dec 2009 13:55:19 -0500